VAPOPREX LVP

Low pressure steam boiler with three flue passes, two in furnace

  • VAPOPREX LVP

Low pressure saturated steam generator with flame reversal, packaged steel structure with pressurised combustion and high energy efficiency. Ready for operation in combination with a jet burner on liquid or gas fuel. Furnace with flame reversal and combustion chamber with cooled end plate sized to ensure low heating loads.

Range consisting of 7 models with useful heat outputs from 1,006 kW to 2,682 kW.


  • Technical Data

    Standard design pressure 0.98 bars.

    Steam production from 1,500 to 4,000 kg/h (up to 2,000 kg/h of steam with complete exemption from certified operator requirements).

    The door is hinged to the tube plate; it’s insulated on the insi-de with a suitable layer of refractory concrete and covers the entire heated surface of the tube plate.

    Amply sized evaporating chamber with large heat exchange area for the production of high quality saturated steam.

    Heat loss to the surrounding environment is limited by a layer of high-density mineral wool on the boiler body, without thermal bridges, protected by stainless steel plate (AISI 430).

    The parts subject to pressure are all welded by qualified and IIS approved personnel, according to EN standards.


    These modern-concept and high-efficiency steam generators have been designed and developed in compliance with European Directive 2014/68/UE(PED) and the most recent national and European standards on pressurised recipients.

    The water circuit can be inspected through a manhole at the top of the boiler and a hand opening ring at the bottom.
     

    CERTIFICATION
    CE mark in accordance with the following directives
    Pressure Equipment (2014/68/UE)
    Low Voltage (2014/35/UE)
    Electromagnetic Compatibility (2014/30/UE)

     


    ACCESSORIES AVAILABLE ON REQUEST


    Economiser: a water-flue gas heat exchanger that increases efficiency by up to 5%. Its configuration and position are defined based on customer requirements.

    Ladder and walkway for safe access to the walkable platform on top of the boiler.

    Modulating supply system with inverter pump for optimum water level management in combination with an economiser.

    Burner: brand and type chosen based on customer specifications.

    Perforated burner plate based on customer specifications.

    Second standby supply pump with valves.

    Second level gauge with valves.

    System for automatically draining
    sludge and dissolved salts that deposit on the bottom.

    Salinity (TDS) control system that measures dissolved salts in the water.

    Cooling tank
    for sampling boiler water.

    BMS 24H for up to 24 hours’ continuous unsupervised operation.

    BMS 72H for up to 72 hours’ continuous unsupervised operation.

    Second FAIL SAFE minimum level probe.

    FAIL SAFE maximum level probe.


    B.E.C.S. (Boiler Electronic Configurable System): the B.E.C.S. control system consists of a PLC fitted with high performance Touch Panel colour operator interface. The interface can be used to manage operation of the Boiler-Burner-Central Heating System.

    “VRC” condensate collection vessel.

    “VRD” atmospheric degasser.

    “BDV” drainage cooling tank.

    Water treatment system.

    Steam manifold.

  • Depliant

Related products

Pic
VAPOPREX LVPq
Low pressure steam boiler with three flue passes, two in furnace
Pic
VAPOPREX HVP
Medium pressure steam generator with three flue passes, two in furnace
Pic
VP 3G
Medium pressure steam boiler with three flue passes
Pic
VAPOPREX 3GF
Medium pressure steam boiler with three flue passes