TP3 Cond

Condensing generator with three flue passes

  • TP3 Cond
  • TP Cond2
  • TP Cond2

Ranges

Models Available from 65kw to 2600kw 

Horizontal condensing generator for pressurised combustion with three flue gas passes and four-star certified energy efficiency in accordance with directive EN 15502-1.

Ready for operation in combination with a jet burner on gas fuel. The arrangement and generous sizing of the combustion chamber guarantee a low heating load and the possibility to be combined with burners featuring technology for the combustion with low polluting emissions.

Range consisting of 7 models with rated outputs from 820 to 2,600 kW.

Note :The TP3 COND Boiler is supplied with Controller – Part no:- 0Q2K10XA, please click Technical Files to see details TP3 Cond Control Panel (1654724151.pdf)

 

 

 


  • Technical Data

    - High-water steel condensing boiler, ready to be coupling with oil or gas jet burner

    - Three flue gas passes:

    * Floating combustion chamber with cooled end plate and a very low volumetric heating

    * Big pipe for the second pass in INOX 2205; with the flue gas recovery from the bottom of the combustion chamber

    * Tube bundle for the third flue gas pass in INOX 2205 to ensure the highest resistance to corrosive condensation; located at the lower part of the hot water generator, fitted with steel inox turbulators to increase convective heat exchange and the condensing process.

    - Front door with reversible opening from both sides and innovative closing system with four micrometric adjustment on the boiler body. Heat insulation using material with excellent insulting properties and reduced thermal inertia, protected by refractory material on the furnace side and on the flue gas pass side.

    - Double heating system return for a correct installation with the low and medium temperature returns. All models of the series have flanged fittings complete with counterflanges

    - Very small frontal size for an easy access to the thermal power station

    - High efficency system

    - Maximum operating pressure 6 bar

    - Maximum design temperature 100°C

    - Satellite control panel in two versions: thermostatic or electronic

     

    Model
    65
    100
    150
    230
    370
    500
    650
    ERP class
     
    A
    -
    -
    -
    -
    -
    -
    Thermal input power (kW)
     
    Max
    61,3
    94,3
    141,5
    217
    349,1
    471,7
    613,2
     
    Min
    18,4
    28,3
    42,5
    65,1
    104,7
    141,5
    184
    Thermal output power (80/60°C) (kW)
     
    Max
    59,5
    91,5
    137,3
    210,5
    338,6
    457,5
    594,8
     
    Min
    18
    27,7
    41,6
    63,8
    102,6
    138,7
    180,3
    Thermal output power (50/30°C)
    (kW)
    Gas
    Max
    65
    100
    150
    230
    370
    500
    650
    Min
    19,7
    30,3
    45,4
    69,7
    112
    151,4
    196,8
    Oil
    Max
    62,9
    96,7
    145
    222,4
    357,8
    483,5
    628,5
    Min
    19,1
    29,4
    44,2
    67,7
    108,9
    147,2
    191,3
     
    Efficency (50/30°C) (%)
    Gas
    Max
    106
    106
    106
    106
    106
    106
    106
    Min
    107
    107
    107
    107
    107
    107
    107
    Oil
    Max
    102,5
    102,5
    102,5
    102,5
    102,5
    102,5
    102,5
    Min
    104
    104
    104
    104
    104
    104
    104
    Efficency 30%
    Gas
    Max
    107,5
    107,5
    107,5
    107,5
    107,5
    107,5
    107,5
    Oil
    Min
    104,5
    104,5
    104,5
    104,5
    104,5
    104,5
    104,5
    Maximun operating pressure
     
    bar
    6
    6
    6
    6
    6
    6
    6
    Loss pressure water side
     
    mbar
    0,4
    0,65
    1,7
    1,7
    2
    3,5
    4,2
    Protection rating
     
     
    IPX0D
    Electrical power supply
     
    V/Hz
    230/50
    230/50
    230/50
    230/50
    230/50
    230/50
    230/50
    Empty weight
     
    Kg
    377
    436
    490
    645
    1035
    1338
    1451
    code
    0rgZ3aXa
    0rgZ4aXa
    0rgZ5aXa
    0rgZ8aXa
    0rgZbaXa
    0rgZdaXa
    0rgZgaXa
    Thermostatic control board code
    0q2k09Xa
    EBM ELECTRONIC CONTROLLER 
    0qc070Xa

     

  • Technical Files
  • Manuals

Related products

Pic
ATLAS D
Forced draft & pressure jet floor standing boiler
Pic
ATLAS A
Forced draft & pressure jet floor standing boiler
Pic
GN2
Forced draft & pressure jet floor standing boiler
Pic
GN4
Forced draft & pressure jet floor standing boiler